Товаров
  
корзина пуста
  • Каталог оборудования Siemens

1-phase, 24 V DC (for S7-300 and ET200M)

  • Заказные данные
    (5)
  • Аксессуары
    (2)
  • Информационные материалы

    Информационные материалы

    The design and functionality of the SIMATIC PS 307 single-phase load power supply (system and load current supply) with automatic range switchover of the input voltage is an optimal match to the SIMATIC S7-300 PLC. By means of the connecting comb that is supplied with the system and load current supply, the supply to the CPU is quickly established. It is also possible to provide a 24 V supply to other S7-300 system components, input/output circuits of the input/output modules and, if necessary, the sensors and actuators. Comprehensive certifications, such as UL, ATEX or GL facilitate universal use (does not apply to outdoor use).

    Дизайн

    • The system and load current supplies are screwed directly onto the S7-300 standard mounting rail and can be mounted directly to the left of the CPU (no installation clearance required)
    • Diagnostic LED for indicating “Output voltage 24 V DC O.K."
    • ON/OFF switches (operation/stand-by) for possible swapping of modules
    • Strain-relief assembly for input voltage connection cable

    Функции

    • Connection to all 1-phase 50/60 Hz networks (120 / 230 V AC) through automatic range switching (PS307) or manual switching (PS307, outdoor)
    • Short-term power failure backup
    • Output voltage 24 V DC, stabilized, short circuit-proof, open circuit-proof
    • Parallel connection of two power supplies for enhanced performance

    Технические данные

    Order number

    6ES7307-1BA01-0AA0

    6ES7305-1BA80-0AA0

    6ES7307-1EA01-0AA0

    6ES7307-1EA80-0AA0

    6ES7307-1KA02-0AA0

    Product

    PS 307

    PS 305 Outdoor

    PS 307

    PS 307 Outdoor

    PS 307

    Power supply, type

    24 V/2 A

    24 V/2 A

    24 V/5 A

    24 V/5 A

    24 V/10 A

    Input

     

     

     

     

     

    Input

    1-phase AC

    DC voltage

    1-phase AC

    1-phase AC

    1-phase AC

    Supply voltage

     

     

     

     

     

    • 1 at AC Rated value

    120 V

    120 V

    120 V

    120 V

    • 2 at AC Rated value

    230 V

    230 V

    230 V

    230 V

    • at DC

    24 ... 110 V

    • Note

    Automatic range selection

    Automatic range selection

    Set by means of selector switch on the device

    Automatic range selection

    Input voltage

     

     

     

     

     

    • 1 at AC

    85 ... 132 V

    85 ... 132 V

    93 ... 132 V

    85 ... 132 V

    • 2 at AC

    170 ... 264 V

    170 ... 264 V

    187 ... 264 V

    170 ... 264 V

    • at DC

    16.8 ... 138 V

    Wide-range input

    No

    Yes

    No

    No

    No

    Overvoltage resistance

    2.3 × Vin rated, 1.3 ms

    154 V; 0.1 s

    2.3 × Vin rated, 1.3 ms

    2.3 × Vin rated, 1.3 ms

    2.3 × Vin rated, 1.3 ms

    Mains buffering at Iout rated, min.

    20 ms; at Vin = 93/187 V

    10 ms; at Vin rated

    20 ms; at Vin = 93/187 V

    20 ms; at Vin = 93/187 V

    20 ms; at Vin = 93/187 V

    Rated line frequency 1

    50 Hz

    50 Hz

    50 Hz

    50 Hz

    Rated line frequency 2

    60 Hz

    60 Hz

    60 Hz

    60 Hz

    Rated line range

    47 ... 63 Hz

    47 ... 63 Hz

    47 ... 63 Hz

    47 ... 63 Hz

    Input current

     

     

     

     

     

    • at rated input voltage 120 V

    0.9 A

    2.3 A

    2.1 A

    4.2 A

    • at rated input voltage 230 V

    0.5 A

    1.2 A

    1.2 A

    1.9 A

    • at rated input voltage 24 V

    2.4 A

    • at rated input voltage 110 V

    0.6 A

    Switch-on current limiting (+25 °C), max.

    22 A

    20 A

    20 A

    45 A

    55 A

    Duration of inrush current limiting at 25 °C

     

     

     

     

     

    • maximum

    3 ms

    10 ms

    3 ms

    3 ms

    3 ms

    I²t, max.

    1 A²·s

    5 A²·s

    1.2 A²·s

    1.8 A²·s

    3.3 A²·s

    Built-in incoming fuse

    T 1.6 A/250 V (not accessible)

    T 6.3 A/250 V (not accessible)

    T 3,15 A/250 V (not accessible)

    T 3,15 A/250 V (not accessible)

    T 6.3 A/250 V (not accessible)

    Protection in the mains power input (IEC 898)

    Recommended miniature circuit breaker: 3 A characteristic C

    Recommended miniature circuit breaker: from 10 A characteristic C, suitable for DC

    Recommended miniature circuit breaker: from 6 A characteristic C

    Recommended miniature circuit breaker: from 10 A characteristic C or from 6 A characteristic D

    Recommended miniature circuit breaker: from 10 A characteristic C

    Output

     

     

     

     

     

    Output

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Rated voltage Vout DC

    24 V

    24 V

    24 V

    24 V

    24 V

    Total tolerance, static ±

    3 %

    3 %

    3 %

    3 %

    3 %

    Static mains compensation, approx.

    0.1 %

    0.2 %

    0.1 %

    0.2 %

    0.1 %

    Static load balancing, approx.

    0.2 %

    0.4 %

    0.5 %

    0.4 %

    0.5 %

    Residual ripple peak-peak, max.

    50 mV

    150 mV

    50 mV

    150 mV

    50 mV

    Residual ripple peak-peak, typ.

    5 mV

    30 mV

    10 mV

    40 mV

    15 mV

    Spikes peak-peak, max. (bandwidth: 20 MHz)

    150 mV

    240 mV

    150 mV

    240 mV

    150 mV

    Spikes peak-peak, typ. (bandwidth: 20 MHz)

    20 mV

    150 mV

    20 mV

    90 mV

    60 mV

    Product function Output voltage adjustable

    No

    No

    No

    No

    No

    Output voltage setting

    -

    -

    -

    -

    -

    Status display

    Green LED for 24 V OK

    Green LED for 24 V OK

    Green LED for 24 V OK

    Green LED for 24 V OK

    Green LED for 24 V OK

    On/off behavior

    No overshoot of Vout (soft start)

    No overshoot of Vout (soft start)

    No overshoot of Vout (soft start)

    No overshoot of Vout (soft start)

    No overshoot of Vout (soft start)

    Startup delay, max.

    2 s

    3 s

    2 s

    3 s

    2 s

    Voltage rise, typ.

    10 ms

    5 ms

    10 ms

    100 ms

    10 ms

    Rated current value Iout rated

    2 A

    2 A

    5 A

    5 A

    10 A

    Current range

    0 ... 2 A

    0 ... 3 A

    0 ... 5 A

    0 ... 5 A

    0 ... 10 A

    • Note

    3 A up to +60°C at Vin > 24 V

    Supplied active power typical

    48 W

    48 W

    120 W

    120 W

    240 W

    Short-term overload current

     

     

     

     

     

    • on short-circuiting during the start-up typical

    9 A

    9 A

    20 A

    20 A

    38 A

    • at short-circuit during operation typical

    9 A

    9 A

    20 A

    20 A

    38 A

    Duration of overloading capability for excess current

     

     

     

     

     

    • on short-circuiting during the start-up

    90 ms

    270 ms

    100 ms

    180 ms

    80 ms

    • at short-circuit during operation

    90 ms

    270 ms

    100 ms

    80 ms

    80 ms

    Parallel switching for enhanced performance

    Yes

    Yes

    Yes

    No

    Yes

    Numbers of parallel switchable units for enhanced performance

    2

    2

    Efficiency

     

     

     

     

     

    Efficiency at Vout rated, Iout rated, approx.

    84 %

    75 %

    87 %

    84 %

    90 %

    Power loss at Vout rated, Iout rated, approx.

    9 W

    16 W

    18 W

    23 W

    27 W

    Closed-loop control

     

     

     

     

     

    Dynamic mains compensation (Vin rated ±15 %), max.

    0.1 %

    0.3 %

    0.1 %

    0.3 %

    0.1 %

    Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.

    0.8 %

    2.5 %

    1 %

    3 %

    2 %

    Load step setting time 50 to 100%, typ.

    0.5 ms

    2.5 ms

    0.3 ms

    0.2 ms

    Load step setting time 100 to 50%, typ.

    0.5 ms

    2.5 ms

    0.3 ms

    0.2 ms

    Setting time maximum

    1 ms

    5 ms

    5 ms

    0.1 ms

    Protection and monitoring

     

     

     

     

     

    Output overvoltage protection

    Additional control loop, shutdown at < 28.8 V, automatic restart

    Additional control loop, shutdown at approx. 30 V, automatic restart

    Additional control loop, shutdown at < 28.8 V, automatic restart

    Additional control loop, shutdown at approx. 30 V, automatic restart

    Additional control loop, shutdown at < 28.8 V, automatic restart

    Current limitation

    2.2 ... 2.6 A

    3.3 ... 3.9 A

    5.5 ... 6.5 A

    5.5 ... 6.5 A

    11 ... 12 A

    Property of the output Short-circuit proof

    Yes

    Yes

    Yes

    Yes

    Yes

    Short-circuit protection

    Electronic shutdown, automatic restart

    Electronic shutdown, automatic restart

    Electronic shutdown, automatic restart

    Electronic shutdown, automatic restart

    Electronic shutdown, automatic restart

    Enduring short circuit current RMS value

     

     

     

     

     

    • maximum

    2 A

    2 A

    7 A

    5 A

    12 A

    Overload/short-circuit indicator

    -

    -

    -

    Safety

     

     

     

     

     

    Primary/secondary isolation

    Yes

    Yes

    Yes

    Yes

    Yes

    Galvanic isolation

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Safety extra low output voltage Vout according to EN 60950-1 and EN 50178, creepage distances and clearances > 5 mm

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Safety extra low output voltage Vout according to EN 60950-1 and EN 50178, creepage distances and clearances > 5 mm

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178

    Protection class

    Class I

    Class I

    Class I

    Class I

    Class I

    Leakage current

     

     

     

     

     

    • maximum

    3.5 mA

    3.5 mA

    3.5 mA

    3.5 mA

    • typical

    0.5 mA

    0.5 mA

    0.3 mA

    0.6 mA

    CE mark

    Yes

    Yes

    Yes

    Yes

    Yes

    UL/cUL (CSA) approval

    cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289

    UL-Listed (UL 508), File E143289, CSA (CSA C22.2 No. 142)

    cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289

    UL-Listed (UL 508), File E143289, CSA (CSA C22.2 No. 142)

    cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289

    Explosion protection

    ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455

    -

    ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455

    -

    ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455

    FM approval

    Class I, Div. 2, Group ABCD, T4

    -

    Class I, Div. 2, Group ABCD, T4

    -

    Class I, Div. 2, Group ABCD, T4

    CB approval

    No

    No

    No

    No

    No

    Marine approval

    In S7-300 system

    -

    In S7-300 system

    -

    In S7-300 system

    Degree of protection (EN 60529)

    IP20

    IP20

    IP20

    IP20

    IP20

    EMC

     

     

     

     

     

    Emitted interference

    EN 55022 Class B

    EN 55011 Class A

    EN 55022 Class B

    EN 55011 Class A

    EN 55022 Class B

    Supply harmonics limitation

    not applicable

    not applicable

    EN 61000-3-2

    -

    EN 61000-3-2

    Noise immunity

    EN 61000-6-2

    EN 61000-6-2

    EN 61000-6-2

    EN 61000-6-2

    EN 61000-6-2

    Operating data

     

     

     

     

     

    Ambient temperature

     

     

     

     

     

    • during operation

    0 ... 60 °C

    -25 ... +70 °C

    0 ... 60 °C

    -25 ... +70 °C

    0 ... 60 °C

    • Note

    with natural convection

    with natural convection

    with natural convection

    with natural convection

    with natural convection

    • during transport

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    • during storage

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    -40 ... +85 °C

    Humidity class according to EN 60721

    Climate class 3K3, no condensation

    Climate class 3K5, transient condensation permitted

    Climate class 3K3, no condensation

    Climate class 3K5, transient condensation permitted

    Climate class 3K3, no condensation

    Mechanics

     

     

     

     

     

    Connection technology

    screw-type terminals

    screw-type terminals

    screw-type terminals

    screw-type terminals

    screw-type terminals

    Connections

     

     

     

     

     

    • Supply input

    L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded

    L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded

    L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded

    L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded

    L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded

    • Output

    L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²

    L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²

    L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²

    L+, M: 3 screw terminals each for 0.5 ... 2.5 mm²

    L+, M: 4 screw terminals each for 0.5 ... 2.5 mm²

    • Auxiliary

    -

    -

    -

    -

    -

    Width of the enclosure

    40 mm

    80 mm

    60 mm

    80 mm

    80 mm

    Height of the enclosure

    125 mm

    125 mm

    125 mm

    125 mm

    125 mm

    Depth of the enclosure

    120 mm

    120 mm

    120 mm

    120 mm

    120 mm

    Required spacing

     

     

     

     

     

    • top

    40 mm

    50 mm

    40 mm

    50 mm

    40 mm

    • bottom

    40 mm

    50 mm

    40 mm

    50 mm

    40 mm

    • left

    0 mm

    0 mm

    0 mm

    0 mm

    0 mm

    • right

    0 mm

    0 mm

    0 mm

    0 mm

    0 mm

    Weight, approx.

    0.4 kg

    0.57 kg

    0.6 kg

    0.57 kg

    0.8 kg

    Product feature of the enclosure housing for side-by-side mounting

    Yes

    Yes

    Yes

    Yes

    Yes

    Installation

    Can be mounted onto S7 rail

    Can be mounted onto S7 rail

    Can be mounted onto S7 rail

    Can be mounted onto S7 rail

    Can be mounted onto S7 rail

    Mechanical accessories

    Mounting adapter for standard mounting rail (6EP1971-1BA00)

    Mounting adapter for standard mounting rail (6ES7390-6BA00-0AA0)

    Mounting adapter for standard mounting rail (6EP1971-1BA00)

    Mounting adapter for standard mounting rail (6ES7390-6BA00-0AA0)

    Mounting adapter for standard mounting rail (6EP1971-1BA00)

    MTBF at 40 °C

    2 320 078 h

    964 506 h

    2 480 589 h

    2 231 610 h

    1 504 280 h

    Other information

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)