    The design and functionality of the SIMATIC PM 1507 single-phase load power supply (PM = power module) with automatic range selection of the input voltage makes it an optimal match to the SIMATIC S7-1500 PLC. It supplies the S7-1500 system components such as CPU, system power supply (PS), I/O circuits of the input and output modules and, if necessary, the sensors and actuators with 24 V DC.

    Дизайн

    • The load current supplies are directly fastened to the S7-1500 mounting rail (without connection to the backplane bus) and can be mounted directly to the left of the CPU (no installation clearance required)
    • Diagnostics LEDs to indicate status and faults: Operation, Fault, Stand-by
    • ON/OFF switches (operation/stand-by) in case of swapping modules
    • Mains connection plug with touch protection and strain relief for connection of input voltage (enables permanent wiring)
    • Plug-in 24 V DC output terminal with reverse polarity protection for connection of 24 V loads (enables permanent wiring)

    Функции

    • Connection to all 1-phase 50/60 Hz networks (120 / 230 V AC) through automatic range switching
    • Short-term mains buffering
    • Output voltage of 24 V DC that is limited to maximum 28 V DC (prevents any damages in 24 V loads if input voltage is too high)
    • 50% "Extra Power" for 5 seconds per minute for short-term overloads, for example, when switching on 24V consumers

    Технические данные

    Order number

    6EP1332-4BA00

    6EP1333-4BA00

    Product

    S7-1500 PM1507

    S7-1500 PM1507

    Power supply, type

    24 V/3 A

    24 V/8 A

    Input

     

     

    Input

    1-phase AC

    1-phase AC

    Supply voltage

     

     

    • 1 at AC Rated value

    120 V

    120 V

    • 2 at AC Rated value

    230 V

    230 V

    • Note

    Automatic range selection

    Automatic range selection

    Input voltage

     

     

    • 1 at AC

    85 ... 132 V

    85 ... 132 V

    • 2 at AC

    170 ... 264 V

    170 ... 264 V

    Wide-range input

    No

    No

    Overvoltage resistance

    2.3 × Vin rated, 1.3 ms

    2.3 × Vin rated, 1.3 ms

    Mains buffering at Iout rated, min.

    20 ms; at Vin = 93/187 V

    20 ms; at Vin = 93/187 V

    Rated line frequency 1

    50 Hz

    50 Hz

    Rated line frequency 2

    60 Hz

    60 Hz

    Rated line range

    45 ... 65 Hz

    45 ... 65 Hz

    Input current

     

     

    • at rated input voltage 120 V

    1.4 A

    3.7 A

    • at rated input voltage 230 V

    0.8 A

    1.7 A

    Switch-on current limiting (+25 °C), max.

    23 A

    62 A

    Duration of inrush current limiting at 25 °C

     

     

    • maximum

    3 ms

    3 ms

    I²t, max.

    1.3 A²·s

    12 A²·s

    Built-in incoming fuse

    T 3,15 A/250 V (not accessible)

    T 6.3 A/250 V (not accessible)

    Protection in the mains power input (IEC 898)

    Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C

    Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C

    Output

     

     

    Output

    Controlled, isolated DC voltage

    Controlled, isolated DC voltage

    Rated voltage Vout DC

    24 V

    24 V

    Total tolerance, static ±

    1 %

    1 %

    Static mains compensation, approx.

    0.1 %

    0.1 %

    Static load balancing, approx.

    0.1 %

    0.1 %

    Residual ripple peak-peak, max.

    50 mV

    50 mV

    Spikes peak-peak, max. (bandwidth: 20 MHz)

    150 mV

    150 mV

    Product function Output voltage adjustable

    No

    No

    Status display

    LED green for 24 V OK; LED red for error; LED yellow for stand-by

    LED green for 24 V OK; LED red for error; LED yellow for stand-by

    On/off behavior

    No overshoot of Vout (soft start)

    No overshoot of Vout (soft start)

    Startup delay, max.

    1.5 s

    1.5 s

    Voltage rise, typ.

    10 ms

    10 ms

    Rated current value Iout rated

    3 A

    8 A

    Current range

    0 ... 3 A

    0 ... 8 A

    Supplied active power typical

    72 W

    192 W

    Short-term overload current

     

     

    • on short-circuiting during the start-up typical

    12 A

    35 A

    • at short-circuit during operation typical

    12 A

    35 A

    Duration of overloading capability for excess current

     

     

    • on short-circuiting during the start-up

    70 ms

    70 ms

    • at short-circuit during operation

    70 ms

    70 ms

    Parallel switching for enhanced performance

    No

    No

    Efficiency

     

     

    Efficiency at Vout rated, Iout rated, approx.

    87 %

    90 %

    Power loss at Vout rated, Iout rated, approx.

    11 W

    21 W

    Closed-loop control

     

     

    Dynamic mains compensation (Vin rated ±15 %), max.

    0.1 %

    0.1 %

    Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.

    1 %

    2 %

    Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.

    3 %

    3 %

    Load step setting time 10 to 90%, typ.

    5 ms

    5 ms

    Load step setting time 90 to 10%, typ.

    5 ms

    5 ms

    Setting time maximum

    5 ms

    5 ms

    Protection and monitoring

     

     

    Output overvoltage protection

    Additional control loop, limitation (closed loop control) at < 28.8 V

    Additional control loop, limitation (closed loop control) at < 28.8 V

    Current limitation

    3.15 ... 3.6 A

    8.4 ... 9.6 A

    Current limitation, typ.

    3.4 A

    9 A

    Property of the output Short-circuit proof

    Yes

    Yes

    Short-circuit protection

    Electronic shutdown, automatic restart

    Electronic shutdown, automatic restart

    Overload/short-circuit indicator

    -

    -

    Safety

     

     

    Primary/secondary isolation

    Yes

    Yes

    Galvanic isolation

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2

    Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2

    Protection class

    Class I

    Class I

    Leakage current

     

     

    • maximum

    3.5 mA

    3.5 mA

    • typical

    0.4 mA

    1.3 mA

    CE mark

    Yes

    Yes

    UL/cUL (CSA) approval

    cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289

    cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289

    Explosion protection

    IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455

    IECEx Ex nA nC IIC T3 Gc; ATEX (EX) II 3G Ex nA nC IIC T3 Gc; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T3, File E330455

    FM approval

    Class I, Div. 2, Group ABCD, T4

    Class I, Div. 2, Group ABCD, T4

    CB approval

    Yes

    Yes

    Marine approval

    GL, ABS, BV, DNV

    GL, ABS, BV, DNV

    Degree of protection (EN 60529)

    IP20

    IP20

    EMC

     

     

    Emitted interference

    EN 55022 Class B

    EN 55022 Class B

    Supply harmonics limitation

    EN 61000-3-2

    EN 61000-3-2

    Noise immunity

    EN 61000-6-2

    EN 61000-6-2

    Operating data

     

     

    Ambient temperature

     

     

    • during operation

    0 ... 60 °C

    0 ... 60 °C

    • Note

    with natural convection

    with natural convection

    • during transport

    -40 ... +85 °C

    -40 ... +85 °C

    • during storage

    -40 ... +85 °C

    -40 ... +85 °C

    Humidity class according to EN 60721

    Climate class 3K3, no condensation

    Climate class 3K3, no condensation

    Mechanics

     

     

    Connection technology

    Screw-/spring clamp connection

    Screw-/spring clamp connection

    Connections

     

     

    • Supply input

    L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²

    L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²

    • Output

    L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²

    L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²

    Product function

     

     

    • removable terminal at input

    Yes

    Yes

    • removable terminal at output

    Yes

    Yes

    Width of the enclosure

    50 mm

    75 mm

    Height of the enclosure

    147 mm

    147 mm

    Depth of the enclosure

    129 mm

    129 mm

    Required spacing

     

     

    • top

    50 mm

    • bottom

    50 mm

    • left

    0 mm

    • right

    0 mm

    Weight, approx.

    0.45 kg

    0.74 kg

    Product feature of the enclosure housing for side-by-side mounting

    Yes

    Yes

    Installation

    Can be mounted onto S7-1500 rail

    Can be mounted onto S7-1500 rail

    MTBF at 40 °C

    1 611 993 h

    1 362 918 h

    Other information

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

    Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)


    Дополнительно

    Power connector

    6ES7590-8AA00-0AA0

    With coding element for power supply module; spare part,
    10 units per packaging unit