SM 431 analog input module

  • Заказные данные
    (7)
  • Аксессуары
    (26)
  • Информационные материалы

    Информационные материалы

    • Analog inputs for the SIMATIC S7-400
    • For connection of voltage and current sensors, thermocouples, resistors and resistance thermometers
    • Resolution from 13 to 16 bit

    Область применения

    Analog input modules can be used to connect the control to analog process signals. They are suitable for the connection of voltage and current sensors, thermocouples, resistors and resistance thermometers.

    Дизайн

    The analog input modules have the following mechanical features:

    • Compact configuration:
      The rugged plastic housing contains:
      • Slot for front connector
      • Labeling strips
    • Simple assembly
    • User-friendly wiring:
      The modules are wired by means of a plug-in front connector.

    Функции

    Analog input modules convert analog signals from the process into digital values for internal processing within the S7-400.

    The modules feature the following:

    • Resolution from 13 to 16 bit
    • Different measurement ranges
    • Alarm functionality
    • Diagnostics

    Технические данные

    Order number

    6ES7431-0HH00-0AB0

    6ES7431-1KF20-0AB0

    6ES7431-1KF00-0AB0

    6ES7431-1KF10-0AB0

    SIMATIC S7-400, ANALOG INPUT

    SIMATIC S7-400, SM 431

    SIMATIC S7-400, SM 431

    SIMATIC S7-400, SM 431

    Supply voltage

     

     

     

     

    Load voltage L+

     

     

     

     

    • Rated value (DC)

    24 V; Only required for supplying 2-wire transmitters

    24 V; Only required for supplying 2-wire transmitters

    not necessary

    24 V; Only required for supplying 2-wire transmitters

    • Reverse polarity protection

    Yes

    Yes

    Yes

    Input current

     

     

     

     

    from load voltage L+ (without load), max.

    400 mA; for 16 connected, fully controlled 2-wire transmitters

    200 mA; for 8 connected, fully controlled 2-wire transmitters

    200 mA; for 8 connected, fully controlled 2-wire transmitters

    from backplane bus 5 V DC, max.

    100 mA

    1 000 mA

    350 mA

    600 mA

    Power loss

     

     

     

     

    Power loss, typ.

    2 W

    4.9 W

    1.8 W

    3.5 W

    Analog inputs

     

     

     

     

    Number of analog inputs

    16

    8

    8

    8

    • For voltage/current measurement

    16

    8

    8

    8

    • For resistance measurement

    4

    4

    4

    permissible input voltage for voltage input (destruction limit), max.

    20 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20)

    18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20)

    50 V

    18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20)

    permissible input current for current input (destruction limit), max.

    40 mA

    40 mA; Permanent

    50 mA; 40 mA continuous

    40 mA; Permanent

    Input ranges (rated values), voltages

     

     

     

     

    • 1 V to 5 V

    Yes

    Yes

    Yes

    Yes

    • -1 V to +1 V

    Yes

    Yes

    Yes

    Yes

    • -10 V to +10 V

    Yes

    Yes

    Yes

    Yes

    • -2.5 V to +2.5 V

    Yes

    • -250 mV to +250 mV

    Yes

    • -5 V to +5 V

    Yes

    • -500 mV to +500 mV

    Yes

    • -80 mV to +80 mV

    Yes

    Input ranges (rated values), currents

     

     

     

     

    • 0 to 20 mA

    Yes

    • -20 mA to +20 mA

    Yes

    Yes

    Yes

    • 4 mA to 20 mA

    Yes

    Yes

    Yes

    Yes

    Input ranges (rated values), thermocouples

     

     

     

     

    • Type B

    Yes

    • Type E

    Yes

    • Type J

    Yes

    • Type K

    Yes

    • Type L

    Yes

    • Type N

    Yes

    • Type R

    Yes

    • Type S

    Yes

    • Type T

    Yes

    • Type U

    Yes

    Input ranges (rated values), resistance thermometer

     

     

     

     

    • Ni 100

    Yes

    • Ni 1000

    Yes

    • Pt 100

    Yes

    • Pt 1000

    Yes

    • Pt 10000

    Yes

    • Pt 200

    Yes

    • Pt 500

    Yes

    Input ranges (rated values), resistors

     

     

     

     

    • 0 to 48 ohms

    Yes

    • 0 to 150 ohms

    Yes

    • 0 to 300 ohms

    Yes

    • 0 to 600 ohms

    Yes

    Yes

    Yes

    • 0 to 6000 ohms

    Yes; Usable up to 5000 Ohm

    Thermocouple (TC)

     

     

     

     

    Temperature compensation

     

     

     

     

    • internal temperature compensation

    No

    • external temperature compensation with compensations socket

    Yes

    • external temperature compensation with Pt100

    Yes

    • dynamic reference temperature value

    Yes

    Characteristic linearization

     

     

     

     

    • parameterizable

    Yes

    • for thermocouples

    Type B, E, J, K, L, N, R, S, T, U

    • for resistance thermometer

    Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000

    Cable length

     

     

     

     

    • shielded, max.

    200 m

    200 m

    200 m

    200 m; 50 m with thermocouples and input ranges <= 80 mV

    Analog value generation for the inputs

     

     

     

     

    Integration and conversion time/resolution per channel

     

     

     

     

    • Resolution with overrange (bit including sign), max.

    13 bit

    14 bit; 14 / 14 / 14

    13 bit

    14 bit; with activated filtering: 16 bits

    • Integration time, parameterizable

    Yes

    Yes

    Yes

    Yes

    • Basic conversion time (ms)

    55 / 65 ms

    52 µs

    23 / 25 ms

    20.1 / 23.5 ms

    • Integration time (ms)

    50 / 60 ms

    16,7 / 20 ms

    16,7 / 20 ms

    • Basic conversion time, including integration time (ms)

    • additional conversion time for wire-break monitoring

    4,3 ms

    • additional conversion time for resistance measurement

    40.2 / 47 ms

    • additional conversion time for wire-break monitoring and resistance measurement

    5,5 ms

    • Interference voltage suppression for interference frequency f1 in Hz

    50 / 60 Hz

    none / 400 / 60 / 50 Hz

    50 / 60 Hz

    50 / 60 Hz

    Encoder

     

     

     

     

    Connection of signal encoders

     

     

     

     

    • for voltage measurement

    Yes; possible

    Yes; possible

    Yes; possible

    Yes; possible

    • for current measurement as 2-wire transducer

    Yes

    Yes; with external transmitter supply

    Yes

    • for current measurement as 4-wire transducer

    Yes

    Yes

    Yes

    Yes

    • for resistance measurement with two-wire connection

    Yes; Line resistances are also measured

    Yes; Line resistances are also measured

    Yes; Line resistances are also measured

    • for resistance measurement with three-wire connection

    Yes; Line resistances are also measured

    Yes; Line resistances are also measured

    Yes

    • for resistance measurement with four-wire connection

    Yes

    Yes

    Yes

    Errors/accuracies

     

     

     

     

    Operational error limit in overall temperature range

     

     

     

     

    • Voltage, relative to input range, (+/-)

    0.65 %; 1.0% at 1 to 5 V; 0.65% at +/-1 V, +/-10 V

    0.7 %; +/-0.7% at +/-1 V; +/-0.9% at +/-10 V, 1 to 5 V

    1 %; +/-1.0% at +/-1 V; +/-0.6% at +/-10 V; +/-0.7% at 1 to 5 V

    0.38 %; +/-0.38% at +/-80 mV; +/-0.35% at +/-250 mV, +/-500mV, +/-1 V, +/-2,5 V, +/-5 V, 1 to 5 V, +/-10 V

    • Current, relative to input range, (+/-)

    0.65 %

    0.8 %; at +/-20 mA, 4 to 20 mA

    1 %; at +/-20 mA, 4 to 20 mA

    0.35 %; +/-20 mA, 0 to 20 mA, 4 to 20 mA

    • Resistance, relative to input range, (+/-)

    1 %

    1.25 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms)

    0.5 %

    • Resistance thermometer, relative to input range, (+/-)

    0.5 %

    Basic error limit (operational limit at 25 °C)

     

     

     

     

    • Voltage, relative to input range, (+/-)

    0.25 %; 0.5% at 1 to 5 V; 0.25% at +/-1 V, +/-10 V

    0.6 %; 0.6% at +/-1 V; 0.75% at +/-10 V, 1 to 5 V

    0.7 %; 0.7% at +/-1 V; 0.4% at +/-10 V; 0.5% at 1 to 5 V

    0.15 %; +/-0.15% (+/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V); +/-0.17% (+/- 80 mV);

    • Current, relative to input range, (+/-)

    0.25 %; at +/-20 mA, 4 to 20 mA

    0.7 %; at +/-20 mA, 4 to 20 mA

    0.7 %; at +/-20 mA, 4 to 20 mA

    0.15 %; +/-20 mA, 0 to 20 mA, 4 to 20 mA

    • Resistance, relative to input range, (+/-)

    0.7 %; 0 to 600 ohms

    0.8 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms)

    0.15 %; +/-0.15% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 600 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.3% at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms)

    • Resistance thermometer, relative to input range, (+/-)

    0.3 %

    Potential separation

     

     

     

     

    Potential separation analog inputs

     

     

     

     

    • Potential separation analog inputs

    No

    Yes; internal/external

    Yes; internal/external

    Yes; internal/external

    • between the channels

    No

    No

    No

    No

    Isolation

     

     

     

     

    Isolation tested with

    500 V AC/707 V DC, type test

    2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog part and L+/M; 2 120 V DC between analog part and local ground; 2 120 V DC between L+/M and local ground

    2120 V DC between bus and analog part; 500 V DC between bus and local ground; 2120 V DC between analog part and local ground

    2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground

    Dimensions

     

     

     

     

    Width

    25 mm

    25 mm

    25 mm

    25 mm

    Height

    290 mm

    290 mm

    290 mm

    290 mm

    Depth

    210 mm

    210 mm

    210 mm

    210 mm

    Weights

     

     

     

     

    Weight, approx.

    500 g

    500 g

    500 g

    500 g


    Order number

    6ES7431-7QH00-0AB0

    6ES7431-7KF00-0AB0

    6ES7431-7KF10-0AB0

    SIMATIC S7-400, SM 431

    SM 431, 8AI, U/I/THERMO, 16BIT

    SM 431, 8AI, RESIST./PT100, 16BIT,

    Supply voltage

     

     

     

    Load voltage L+

     

     

     

    • Rated value (DC)

    24 V; Only required for supplying 2-wire transmitters

    • Reverse polarity protection

    Yes

    Input current

     

     

     

    from load voltage L+ (without load), max.

    400 mA; for 16 connected, fully controlled 2-wire transmitters

    from backplane bus 5 V DC, max.

    700 mA

    1 200 mA

    650 mA

    Power loss

     

     

     

    Power loss, typ.

    4.5 W

    4.6 W

    3.3 W

    Analog inputs

     

     

     

    Number of analog inputs

    16

    8

    8

    • For voltage/current measurement

    16

    8

    • For resistance measurement

    8

    8

    permissible input voltage for voltage input (destruction limit), max.

    18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20)

    35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)

    35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)

    permissible input current for current input (destruction limit), max.

    40 mA

    32 mA

    Input ranges (rated values), voltages

     

     

     

    • 1 V to 5 V

    Yes

    Yes

    • -1 V to +1 V

    Yes

    Yes

    • -10 V to +10 V

    Yes

    Yes

    • -100 mV to +100 mV

    Yes

    • -2.5 V to +2.5 V

    Yes

    Yes

    • -20 mV to +20 mV

    Yes

    • -25 mV to +25 mV

    Yes

    • -250 mV to +250 mV

    Yes

    Yes

    • -5 V to +5 V

    Yes

    Yes

    • -50 mV to +50 mV

    Yes

    Yes

    • -500 mV to +500 mV

    Yes

    Yes

    • -80 mV to +80 mV

    Yes

    Yes

    Input ranges (rated values), currents

     

     

     

    • 0 to 20 mA

    Yes

    Yes

    • -10 mA to +10 mA

    Yes

    Yes

    • -20 mA to +20 mA

    Yes

    Yes

    • -3.2 mA to +3.2 mA

    Yes

    • 4 mA to 20 mA

    Yes

    Yes

    • -5 mA to +5 mA

    Yes

    Yes

    Input ranges (rated values), thermocouples

     

     

     

    • Type B

    Yes

    Yes

    • Type E

    Yes

    Yes

    • Type J

    Yes

    Yes

    • Type K

    Yes

    Yes

    • Type L

    Yes

    Yes

    • Type N

    Yes

    Yes

    • Type R

    Yes

    Yes

    • Type S

    Yes

    Yes

    • Type T

    Yes

    Yes

    • Type U

    Yes

    Yes

    Input ranges (rated values), resistance thermometer

     

     

     

    • Ni 100

    Yes

    Yes

    • Ni 1000

    Yes

    Yes; Different characteristics selectable: Europe/U.S.

    • Pt 100

    Yes

    Yes

    • Pt 1000

    Yes

    Yes

    • Pt 200

    Yes

    Yes

    • Pt 500

    Yes

    Yes

    Input ranges (rated values), resistors

     

     

     

    • 0 to 48 ohms

    Yes

    • 0 to 150 ohms

    Yes

    • 0 to 300 ohms

    Yes

    • 0 to 600 ohms

    Yes

    • 0 to 6000 ohms

    Yes; Usable up to 5000 Ohm

    Thermocouple (TC)

     

     

     

    Temperature compensation

     

     

     

    • internal temperature compensation

    Yes

    • external temperature compensation with compensations socket

    Yes

    Yes

    • external temperature compensation with Pt100

    Yes

    • dynamic reference temperature value

    Yes

    Yes

    Characteristic linearization

     

     

     

    • parameterizable

    Yes

    Yes

    Yes

    • for thermocouples

    Type B, E, J, K, L, N, R, S, T, U

    Type B, E, J, K, L, N, R, S, T, U

    • for resistance thermometer

    Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000

    Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000; different characteristics selectable (Europe/U.S.)

    Cable length

     

     

     

    • shielded, max.

    200 m; 50 m with thermocouples and input ranges <= 80 mV

    200 m

    200 m; 50 m with thermocouples and input ranges +/-80 mV

    Analog value generation for the inputs

     

     

     

    Integration and conversion time/resolution per channel

     

     

     

    • Resolution with overrange (bit including sign), max.

    16 bit; 16 / 16 / 16

    16 bit

    16 bit

    • Integration time, parameterizable

    Yes

    Yes

    Yes

    • Basic conversion time (ms)

    6 / 20,1 / 23,5 ms

    10 / 16,7 / 20 / 100

    8 / 23 / 25 ms

    • Integration time (ms)

    2,5 / 16,7 / 20 ms

    2,5 / 16,7 / 20 / 100

    20 ms at 50 Hz (entire module incl. wire break)

    • Basic conversion time, including integration time (ms)

    • additional conversion time for wire-break monitoring

    4.3 / 4.3 / 4.3 ms

    110 ms / 4 ms

    • additional conversion time for resistance measurement

    12 / 40,2 / 47 ms

    • additional conversion time for wire-break monitoring and resistance measurement

    5,5 ms

    1 ms (module)

    none

    • Interference voltage suppression for interference frequency f1 in Hz

    400 / 60 / 50 Hz

    400 / 60 / 50 / 10 Hz

    none/ 60 / 50 Hz

    Encoder

     

     

     

    Connection of signal encoders

     

     

     

    • for voltage measurement

    Yes; possible

    Yes; possible

    • for current measurement as 2-wire transducer

    Yes

    • for current measurement as 4-wire transducer

    Yes

    Yes

    • for resistance measurement with two-wire connection

    Yes; Line resistances are also measured

    • for resistance measurement with three-wire connection

    Yes

    Yes

    • for resistance measurement with four-wire connection

    Yes

    Yes

    Yes

    Errors/accuracies

     

     

     

    Operational error limit in overall temperature range

     

     

     

    • Voltage, relative to input range, (+/-)

    0.3 %; +/-0.3% at +/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V; +/-0.31% at +/-80 mV; +/-0.32% at +/-50 mV; +/-0.35% at +/-25 mV;

    0.3 %

    • Current, relative to input range, (+/-)

    0.3 %; at 0 to 20 mA, +/-5 mA, +/-10 mA, +/- 20 mA, 4 to 20 mA

    0.5 %

    • Resistance, relative to input range, (+/-)

    0.3 %; +/-0.3% at 0 to 48 Ohm (4-conductor measurement), 0 to 150 Ohm (4-conductor measurement), 0 to 300 Ohm (4-conductor measurement), 0 to 600 Ohm (4-conductor measurement), 0 to 5000 Ohm (4-conductor measurement, in range of 6000 Ohm); +/-0.4% at 0 to 300 Ohm (3-conductor measurement), 0 to 600 Ohm (3-conductor measurement), 0 to 5000 Ohm (3-conductor measurement, in range of 6000 Ohm);

    • Resistance thermometer, relative to input range, (+/-)

    0.4 %

    +/-1 °C

    Basic error limit (operational limit at 25 °C)

     

     

     

    • Voltage, relative to input range, (+/-)

    0.15 %; ±0.15% at ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 V to 5 V, ±10 V; ±0.17% at ±80 mV; ±0.19% at ±50 mV; ±0.23% at ±25 mV

    0.1 %

    • Current, relative to input range, (+/-)

    0.15 %; at 0 to 20 mA, +/-5 mA, +/-10 mA, +/- 20 mA, 4 to 20 mA

    0.17 %

    • Resistance, relative to input range, (+/-)

    0.15 %; +/-0.15% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.3% at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms)

    • Resistance thermometer, relative to input range, (+/-)

    0.3 %

    +/-0,2 °C

    Interrupts/diagnostics/status information

     

     

     

    Diagnostics

    Yes; Parameterizable

    Yes

    Yes

    Alarms

     

     

     

    • Diagnostic alarm

    Yes; Parameterizable

    Yes; Parameterizable

    Yes; Parameterizable

    • Limit value alarm

    Yes; Parameterizable

    Yes

    Yes

    Potential separation

     

     

     

    Potential separation analog inputs

     

     

     

    • Potential separation analog inputs

    Yes; internal/external

    Yes; internal/external

    Yes; internal/external

    • between the channels

    No

    Yes

    No

    Isolation

     

     

     

    Isolation tested with

    2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground

    1500 V DC

    1500 V DC

    Dimensions

     

     

     

    Width

    25 mm

    25 mm

    25 mm

    Height

    290 mm

    290 mm

    290 mm

    Depth

    210 mm

    210 mm

    210 mm

    Weights

     

     

     

    Weight, approx.

    500 g

    650 g

    650 g


    Дальнейшая информация

    Brochures

    Information material for downloading can be found in the Internet:

    http://www.automation.siemens.com/infocenter